Information service
New standards
This document applies to the connections described in EN 50483-4, including branch connectors, Insulation Piercing Connectors (IPC), pre-insulated lugs (terminals) and through pre-insulated connectors (sleeves).
Two classes of connectors are covered by this document:
- Class A: These are connectors intended for electricity distribution or industrial networks in which they can be subjected to short-circuits of relatively high intensity and duration. As a consequence, Class A connectors will be suitable for the majority of applications.
- Class B: These are connectors for networks in which overloads or short-circuits are rapidly cleared by the operation of protection devices.
Depending on their application, the connectors are subjected to heat cycles and short-circuit current tests.
Class A: the connectors are subjected to heat cycles and short-circuit current tests.
Class B: the connectors are subjected to heat cycles only.
The object of this document is to define the heating cycles test methods and requirements which apply to compression through connectors, insulation piercing connectors and all other type of connections for low voltage aerial bundled cables.
This document applies to connectors used for the electrical connection of ABC.
The connectors are designed to be installed where either the main and/or branch cable is ABC as defined by HD 626 S2.
Tests described in this document are type tests.
This document applies to tensioning devices consisting of tension and suspension clamps, and tension and suspension assemblies used for the installation of ABC with either insulated or bare neutral messenger.
The tension and suspension clamps are designed to be installed on neutral conductors of ABC defined in HD 626 S2.
Tests described in this document are type tests.
This document applies to tensioning devices consisting of tension and suspension clamps, fittings and brackets designed to be used for installation of self-supporting ABC defined in HD 626 S2.
Tests described in this document are type tests.
This document defines the environmental tests in particular the climatic and corrosion ageing tests. The objective of these tests is to predict the behaviour of ABC accessories when subjected to sun radiation, to weather conditions (humidity, spraying water, heat, cold) and pollution. EN 50483-1, EN 50483-2, EN 50483-3 and EN 50483-4 specify which type tests included in this part of the standard are needed.
The purpose of this Part 1 is to define the common aspects of the products included in the above scope.
This document is applicable to generating sets for land and marine use (domestic, recreational and industrial application). This document is not applicable to generating sets used on board of seagoing vessels and mobile offshore units as well as on aircraft or to propel road vehicles and locomotives.
This document is not applicable to gensets and components manufactured before the date of its publication.
NOTE This document does not apply to arc welding equipment (IEC 60974 series).
This document does not specify the special requirements needed to cover operation in potentially explosive atmospheres and is not applicable for such environments.
The hazards relevant to RIC engine driven generating sets are identified in Table A.1.
This document deals with the special requirements of test and safety design which are observed in addition to the definitions and requirements in ISO 8528-1:2018, ISO 8528-2:2018, ISO 8528-3:2020, ISO 8528-4:2025, ISO 8528-5:2025, ISO 8528-6:2023 and ISO 8528-10:2022, where applicable. This document specifies safety requirements in order to protect the user from danger.
IEC 62680-1-2:2026 cancels and replaces the seventh edition published in 2024 and constitutes a technical revision.
Extended Power Range (EPR) including Adjustable Voltage Supply (AVS) has been added. This document is the USB-IF publication Universal Serial Bus Power Delivery Specification Revision 3.2, Version 1.1.
The object of this document is to
- define the terms used,
- specify additional test methods and provide additions and modifications to tests referred,
- specify acceptance criteria.
This document is to be used in addition to the respective product standard applicable to the product, application and design to which the fibre optic element has been added. Furthermore, this document does not include requirements dealing with the choice of insulators for specific operating conditions or environments.
This document aims to serve as knowledge retention, describing the methodologies, investigation, and verification techniques, as well as providing a compendium of the different verification results, of the development of IEC TS 60695-2-21:2023 as new test method.
IEC/TC 89 and other IEC Technical Committees can benefit from this document, when developing new test methodologies or planning and executing round robin tests.
The objective of this document is to address the immediate needs of motor manufacturers striving to achieve high IEC efficiency classes.
IEC TS 63573 is an independent product-specific specification focusing on rotating electrical machines in accordance with the IEC 60034 series and can be applied as a supplement to IEC 60404-8-4.
At the time of publication of this document it is anticipated that collaboration with IEC Technical Committee 68 (Magnetic alloys and steels) will lead to the development of Amendment 2 to IEC 60404-8-4:2022. This amendment is expected to clarify the relevant issues and provide a comprehensive solution.
This Technical Specification will be withdrawn once Amendment 2 to IEC 60404-8-4:2022 is published and takes effect, provided it addresses the identified need.
This document intends, as a contribution to the IEC Common Data Dictionary, to be used by catalogue consortia, other database standards and software as a data reference for circuit‑breakers and similar equipment for household use.
IEC 60245-4:2026 includes the following significant technical changes with respect to the previous edition:
a) reference to tests according to IEC 60245-2 has been deleted and replaced by IEC 63294;
b) normative references have been updated.
This document is to be used in conjunction with IEC 60245-1.
IEC 60245-8:2026 includes the following significant technical changes with respect to the previous edition:
a) reference to IEC 60245-2 for the tests has been deleted and replaced by IEC 63294;
b) reference to lift cable according to IEC 60245-5 has been deleted;
c) normative references have been updated.
This document is to be used in conjunction with IEC 60245-1.
IEC 60947-6-1:2026 applies to transfer switching equipment (TSE), to be used in power systems for ensuring the continuity of the supply and allowing the energy management of the installation, by transferring a load between power supply sources, the rated voltage of which does not exceed 1 000 V AC or 1 500 V DC. Specific requirements for bypass/isolation transfer switch equipment are given in Annex C, ATSE having closed transition capability are given in Annex D, stand-alone ATS controllers are given in Annex E, and TSE for electric driven fire pump controllers are given in Annex F.
It covers:
- manually operated transfer switching equipment (MTSE);
- remotely operated transfer switching equipment (RTSE);
- automatic transfer switching equipment (ATSE), including the controller;
- stand-alone ATS controllers;
- bypass/isolation transfer switch equipment (BTSE);
- ATSE having closed transition capability;
- fire pump TSE.
It does not cover:
- TSE configurations that are not fully manufacturer type tested or marked according to this document as a complete transfer switch;
- auxiliary contacts (for guidance, see IEC 60947-5-1);
- transfer switches used in explosive atmospheres (for guidance, see IEC 60079 (all parts));
- embedded software design (for guidance, see IEC TR 63201);
- cybersecurity aspects (for guidance, see IEC 63208);
- TSE rated for direct-on-line starting asynchronous motor of design NE and HE, according to IEC 60034-12. (for guidance, see AC-3e utilisation category according to IEC 60947 4 1);
- other types of TSE under consideration including overlapping neutral TSE, multi-source TSE (i.e. TSE with more than two sources of supply), TSE with load-shedding functions, bus-tie TSE, and hybrid TSE;
- static transfer switches covered by IEC 62310 series.
This fourth edition cancels and replaces the third edition published in 2021. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
- clarification of scope;
- clarification of terms and definitions;
- Annex C for Bypass/Isolation Transfer Switch Equipment;
- Annex D for ATSE having closed transition capability;
- Annex E for Stand-alone ATS controller;
- Annex F for TSE used with electric driven fire pump control equipment.
This document applies to the identification and marking of terminals of electrical equipment such as resistors, fuses, relays, contactors, transformers, rotating machines and, wherever applicable, to combinations of such equipment (e.g. assemblies), and it also applies to the identification of terminations of certain designated conductors. It also provides general rules for the use of certain colours or alphanumeric notations to identify conductors with the aim of avoiding ambiguity and ensuring safe operation. These conductor colours and alphanumeric notations are intended to be applied on cores, busbars, and electrical equipment, and in cables or installations.
This basic safety publication focusing on safety essential requirements is primarily intended for use by technical committees in the preparation of standards in accordance with the principles laid down in IEC Guide 104 and ISO/IEC Guide 51.
It is not intended for use by manufacturers or certification bodies. One of the responsibilities of a technical committee is, wherever applicable, to make use of basic safety publications in the preparation of its publications. The requirements of this basic safety publication will not apply unless specifically referred to or included in the relevant publications.
This part of IEC 60079 supplements and modifies the general requirements of IEC 60079-0, except as indicated in Table 1. Where a requirement of this part of IEC 60079 conflicts with a requirement of IEC 60079-0, the requirement of this part of IEC 60079 takes precedence.
Replaced standards
It is applicable to generating sets for land and marine use (domestic, recreational and industrial application). It is not applicable to generating sets used on board of seagoing vessels and mobile offshore units as well as on aircraft or to propel road vehicles and locomotives.
NOTE This part of ISO 8528 does not apply to arc welding equipment (IEC 60974 series).
The special requirements needed to cover operation in potentially explosive atmospheres are not covered in this part of ISO 8528.
The hazards relevant to RIC engine driven generating sets are identified in Annex A.
ISO 8528-13:2016 deals with the special requirements of test and safety design which should be observed in addition to the definitions and requirements in ISO 8528-1, ISO 8528-2, ISO 8528-3, ISO 8528-4, ISO 8528-5 and ISO 8528-6, where applicable. It specifies safety requirements in order to protect the user from danger.
This consolidated version consists of the first edition (1998)
and its amendment 1 (2003). Therefore, no need to order amendment in
addition to this publication.
system of the battery. This standard applies to lead-acid batteries (Pb) and nickel-cadmium batteries (Ni-Cd).*
This consolidated version consists of the first edition (1998)
its amendment 1 (2003) and its amendment 2 (2011). Therefore, no
need to order amendments in addition to this publication.
The main changes with respect to the previous edition are as follows:
- updating of the normative references;
- updating of Table 3 and Table 5 on dimensions for type 53 and type 57.
This publication is to be read in conjunction with IEC 60245-1:2003 and IEC 60245-2:1994.
Compliance criteria relating to data sheet parameters in this document are covered by IEC 632201 for safety, or IEC 632212 for performance.
Drafts
metal pipelines influenced by HVDC systems.
It provides guidance on how the design, construction, operation, maintenance, and decommissioning
phases of HVDC systems affect buried metal pipelines.
Electrical interference conditions (AC and DC) to pipeline systems are described, and acceptable levels
of interference are discussed.
Minimum separation distances are recommended.
The following aspects are not covered in this document:
-Contractual responsibilities
-Personnel safety
a) a system with provision for protective earthing and with a rated voltage not exceeding 440 V between poles and where the rated current does not exceed 16 A per conductor, for use with class I and class II luminaires, or
b) a system without provision for protective earthing where protection against electric shock is based on a SELV supply and where the rated current does not exceed 25 A per conductor, for use with class III luminaires, or
c) a combination of a) and b) for connecting both class I and class II luminaires and class III luminaires simultaneously but in different sector openings.”
The track systems can also provide for the mechanical support of the luminaires.
This document applies to track systems designed for ordinary interior use for mounting on, or flush with, or suspended from walls and ceilings. These track systems are not intended for locations where special conditions prevail as in ships, vehicles and the like and in hazardous locations, for example, where explosions are liable to occur.
This document does not cover operational or performance compatibility between different track
systems. Protection against unsafe compatibility between Class I and Class III circuits is covered by this document. In addition to supply circuits, the track system can be provided with auxiliary circuits such as
those for the purpose of a control or audio signal.
NOTE At present, on the market, the following types of control systems are available:
− FELV control signal, basic insulated from mains supply (e.g. Digital Addressable Lighting Interface and 1–10 V DC controls);
− SELV or PELV control signal (e.g. DMX);
− control signal, not insulated from mains supply (e.g. push button control, phase cut, step dim).
Track systems can also be provided with conductors specifically identified for powering emergency lighting luminaires.
This document applies to thermal protectors
• That are integrated or incorporated in ballasts for tubular fluorescent lamps;
• for use in ballasts of tubular fluorescent lamps used by the public , such as equipment intended to be used in shops, offices, hospitals, farms and commercial and industrial
applications;
• that are AC or DC controls with a rated voltage not exceeding 690 V AC or 600 V DC
• using NTC or PTC thermistors and to discrete thermistors, requirements for which are contained in Annex J
• that are electromechanical or electronic in design and responsive to or controlling such characteristics as temperature.”.
NOTE 1 Throughout this document, the word "equipment" means "ballasts for tubular fluorescent lamps" and
“Controls” means “thermal protectors
NOTE 2 Requirements concerning the testing of the combination of ballasts and thermal protectors are given in
IEC 61347-.
This document applies to
– the inherent safety of thermal protectors for ballasts for tubular fluorescent lamps, and
– functional safety of thermal protectors used to protect ballasts for tubular fluorescent lamps from overheating,
– controls where the performance (for example the effect of EMC phenomena) of the product can impair the overall safety and performance of the controlled system,
– the operating values, operating times, and operating sequences where such are associated with equipment safety.
– Thermal protectors for ballasts within the scope of IEC 61347-2-8
– Thermal protectors that may be suitable for ballasts for other discharge lamps such as ballasts under the scope of IEC 61347-2-9
– This document does not apply to
• A manual device for opening the circuit
• Other means used to protect ballasts
a system of interconnected units or of independent units, subject to installing, operating and maintaining the STS in the manner prescribed by the manufacturer.
This document specifies requirements to ensure safety for the ordinary person who comes into contact with the STS and, where specifically stated, for the skilled person. The objective is to reduce risks of fire, electric shock, thermal, energy and mechanical hazards during use and operation and, where specifically stated, during service and maintenance.
This part of IEC 62310 includes requirements for the switching elements, their control and protective elements, where applicable. This part of IEC 62310 also includes information for the overall integration of the STS and its accessories into the low voltage AC power distribution system.
Components or devices necessary for the operation, control, protection and isolation (e.g. circuit breakers, fuses, transformers, relays, etc.) of an STS should comply with the requirements of the relevant IEC standards and are not covered by this part of IEC 62310.
This document is harmonized with the applicable parts of group safety publication IEC 62477-1:2022 for power electronic converter systems and contains additional requirements relevant to STS.
This document does not apply to:
• devices for DC source switching
• transfer switching equipment (TSE) covered by IEC 60947-6-1
• the automatic switching devices integrated into UPS covered by IEC 62040 series
This part of IEC 60079 supplements and modifies the general requirements of IEC 60079-0, except as indicated in Table 1. Where a requirement of this part of IEC 60079 conflicts with a requirement of IEC 60079-0, the requirement of this part of IEC 60079 takes precedence. Where this document makes reference to the requirements of Level of Protection “ec” in IEC 60079-7, the requirements of IEC 60079-7 take precedence.
- co-ordination of protection principles between power supply and traction units, i.e. separation sections, train set current or power limitation, short circuit current discrimination, circuit breaker coordination and use of regenerative braking;
- co-ordination of installed power on the line and the power demand of trains, i.e. traction unit power factor, train set current or power limitation, electric system performance, type and characterization;
- compatibility assessment relating to harmonics and dynamic effects.
Informative values are given for some parts of the existing European railway networks, in annexes.
NOTE For those railways within the scope of EU Interoperability Directive, definitive values are set out in the register of infrastructure published in accordance with Article 49 of Directive (EU) 2016/797, and the list of items included in the register is described in the commission decision (EU) 2019/777.
The following electric traction systems are within the scope of this document:
- railways;
- guided mass transport systems that are integrated with railways;
- material transport systems that are integrated with railways.
Information is given on electrification parameters to enable train operating companies to confirm, after consultation with the rolling stock manufacturers, that risks of non-compatibility are minimized and that there will be no consequential disturbance on the electrification system.
The interaction between pantograph and overhead contact line is dealt with in EN 50367:2020.
The interaction with the control-command and signalling subsystem is not dealt with in this document.
Basic considerations have been included concerning the use of traction units with onboard electric traction energy storage in the electric traction power system. Details of this are dealt with in CLC/TS 50729:2025.
Lighting equipment with a wireless control function are also within the scope of this document. However, the test is limited to the control of the lighting function only. Radio properties like frequency stability or spurious emissions are not assessed.
EXAMPLE Colour/light level control via a wireless interface are meant to stay intact during and after an immunity test.
Also included in the scope of this document is lighting equipment that interfaces with systems or installations other than common power supply networks.
Excluded from the scope of this document are:
– components or modules designed to be integrated into lighting equipment but not intended for end-user replacement.
– equipment for which the electromagnetic compatibility requirements in the radio-frequency range are explicitly formulated in other product immunity standards, even if they incorporate a built-in lighting function.
NOTE 1 Examples of exclusions are: – equipment with built-in lighting devices for display back lighting, scale illumination and signaling;
– SSL-displays;
– range hoods, refrigerators, freezers; – photocopiers, projectors;
– electronic switches for fixed installations;
– lighting equipment for road vehicles (within the scope of CISPR 12);
– lighting equipment for aircraft and airfield facilities.
NOTE 2 Modules that are not end-user replaceable are not in the scope of this document but can be tested according to this document for information purposes (for instance, of luminaire manufacturers).
In multi-function equipment where the lighting function operates independently from other functions, the electromagnetic immunity requirements of this document apply to the lighting function only.
The requirements of this document are based on the generic immunity standard for residential, commercial and light-industrial environments IEC 61000-6-1:2016, but modified to lighting engineering practice.
It can be expected that lighting equipment complying with the requirements of this document will operate satisfactorily in other environments. In some special cases, measures can be taken to provide higher immunity. In this document it is impracticable to deal with all these possibilities.
Such requirements can be established by contractual agreement between supplier and purchaser.
This document does not cover the effects that electromagnetic disturbances have on the lifetime of lighting equipment.
maintenance activities for erection of electrical HV installations to ensure the safety of such systems.
In the context of this document, "safety" relates to the safety of persons, domestic animals, livestock and safe protection of equipment and property.
This GROUP SAFETY PUBLICATION focusing on safety essential requirements is primarily intended to be used as a SAFETY STANDARD for the installations mentioned in the scope, but is also intended to be used by TCs in the preparation of publications for installations similar to
those mentioned in the scope of this GROUP SAFETY PUBLICATION, in accordance with the principles laid down in IEC Guide 104 and lSO/lEC Guide 51.
One of the RESPONSIBILITIES of a TC is, wherever applicable, to make use of BSPs and/or GSPs in the preparation of its publications.