This standard specifies the requirements for shop fabricated cylindrical, horizontal steel tanks, single and double skin for the underground storage of water polluting liquids (both flammable and non-flammable) within the following limits: - from 800 mm up to 3000 mm nominal diameter and,- up to a maximum overall length of 6 times the nominal diameter and,- for liquids with a maximum density of up to 1,9 kg/l and,- with an operating pressure ( po) of maximum 1,5 bar (abs.) and,- for double skin tanks with a vacuum leak detection system where the kinematic viscosity does not exceed 5 x 10-3 m2/s