IEC 61439-4 defines the specific requirements of ACS (assembly for construction site) as follows:
— assemblies for which the rated voltage does not exceed 1 000 V in case of AC or 1 500 V in case of DC,
— assemblies where the nominal primary voltage and the nominal secondary voltage of transformers incorporated in ACS are within the limits specified above,
— assemblies intended for use on construction sites, both indoors and outdoors, i.e. temporary places of work to which the public do not generally have access and where building construction, installation, repairs, alteration or demolition of property (buildings) or civil engineering (public works) or excavation or any other similar operations are carried out,
— transportable (semi-fixed) or mobile assemblies with enclosure.
Note: throughout this document, the abbreviation ACS is used for a low-voltage switchgear and controlgear assembly intended for use on construction and similar sites.
The manufacture or assembly can be carried out by an entity other than by the original manufacturer.
IEC 61439-4 does not apply to individual devices and self-contained components, such as motor starters, fuse switches, electronic equipment, etc. which will comply with the relevant product standards. IEC 61439-4 does not apply to assemblies for use in the administrative centres of construction sites (offices, cloakrooms, meeting rooms, canteens, restaurants, dormitories, toilets, etc.).
Requirements for electrical protection provided by equipment manufactured according to this standard are given in IEC 60364-7-704.
IEC 61439-4:2023 text has been approved in Europe as EN IEC 61439-4:2026 without any changes.